TESTED DEVICE®

Report No.downup Manufacturerdownup Product Namedownup Subject of Test (Result)downup
SI 1506-767 Sika AG floor covering
SR-305 W ESD; SR-269 ECF CR
color: RAL 7032; surface: smooth
SI 1506-767 Sika AG floor covering
Sikafloor-3240
color: RAL 7035; surface: smooth
Biological resistance (ISO 846)
Riboflavin test (VDMA information leaflet)
SI 1412-740 Sika AG Floor covering
Sikafloor-262 AS N
smooth
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 4)
SI 1412-740 Sika AG Floor covering
Sikafloor-268
smooth
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 2)
SI 1403-695 Sika AG Floor covering
Sikafloor-390 N
RAL 7035 (light grey)
Biological resistance (ISO 846)
Particle emission (VDI 2083 part 17) (ISO Class 3)
Riboflavin test (VDMA information leaflet)
SI 1403-695 Sika AG Floor covering
Sikafloor-721 ECF
RAL 7002 (oliv grey)
Biological resistance (ISO 846)
Particle emission (VDI 2083 part 17) (ISO Class 3)
Riboflavin test (VDMA information leaflet)
SI 1403-695 Sika AG Floor covering
Sika-DecoFlake + Sikafloor-316
transparent
Particle emission (VDI 2083 part 17) (ISO Class 8)
SI 1403-695 Sika AG Floor covering
Sika-DecoFloor + Sikafloor-316
transparent
Particle emission (VDI 2083 part 17) (ISO Class 3)
SI 1403-695 Sika AG Floor covering
Sikafloor-21 PurCem
RAL 7032 pebble grey
Particle emission (VDI 2083 part 17) (ISO Class 4)
SI 1403-695 Sika AG Floor covering
Sikafloor-24 PurCem
RAL 7037 dust grey
Biological resistance (ISO 846)
Particle emission (VDI 2083 part 17) (ISO Class 6)
Riboflavin test (VDMA information leaflet)
SI 1212-624 Sika AG Sikafloor-2540 W

Biological resistance (ISO 846)
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 4)
SI 1204-593 Sika AG Floor covering
Sikafloor-390 ECF
Biological resistance (ISO 846)
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 1)
SI 1204-593 Sika AG Floor covering
Sikafloor-264 Thixo
Particle emission (VDI 2083 part 17)
SI 1108-568 Sika AG Floor covering
Sikafloor-326 SL
Biological resistance (ISO 846)
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 4)
SI 1103-544 Sika AG Floor Covering
Sikafloor-325
RAL 7037
Biological resistance (ISO 846)
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 4)
RO 1702-883 Roche Diagnostics GmbH Roche Mannheim Terrazzo LW standard
Surface smooth
Ab- / Desorption kinetic (VDI 2083 part 20 draft)
Biological resistance (ISO 846)
Chemical resistance (VDI 2083 part 17)
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 4)
Riboflavin test (VDMA information leaflet)
RO 1608-853 Roche Diagnostics GmbH Floor covering
PQ18 granite
Ab- / Desorption kinetic (VDI 2083 part 20 draft)
Biological resistance (ISO 846)
Chemical resistance (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 5)
Riboflavin test (VDMA information leaflet)
RO 1608-852 Roche Diagnostics GmbH Floor covering
MP2L stoneware tile
Ab- / Desorption kinetic (VDI 2083 part 20 draft)
Chemical resistance (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 5)
Riboflavin test (VDMA information leaflet)
RO 1608-841 Roche Diagnostics GmbH Floor covering
MP2L joint seal
Ab- / Desorption kinetic (VDI 2083 part 20 draft)
Biological resistance (ISO 846)
Chemical resistance (VDI 2083 part 17)
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 6)
Riboflavin test (VDMA information leaflet)
RE 1411-735 Remmers Baustofftechik GmbH Floor covering
Epoxy ESD Color 3K
Color: Pebble grey
Outgassing (VDI 2083 part 17)
Particle emission (VDI 2083 part 17) (ISO Class 4)
*Extract from VDI 2083 Part 9.1: "This guidline provides definitions of the terms "compatibility with the required cleanliness" and "cleanroom compatibility" and, based on these definitions, the classification and procedures serving to establish the suitability of equipment and air-handling components for use in environments whose air cleanliness and other parameters are assessed in accordance with technical rules (e.g. ISO 14644-1). For the purpose of this guideline, the classification is based on the particle emission.