TESTED DEVICE®

No image available!

Company

StoCretec GmbH
 
Gutenbergstraße 6
65830 Kriftel

Contact Person

Mr. Dr. Michael Kaltenbach
Phone +49-6192401-125
Email m.kaltenbach@stoeu.com
Website https://www.stocretec.de/?gclid=EAIaIQobChMIkIfFiMql8AIVPBoGAB1vrg_3EAAYASAAEgKMwvD_BwE

Test Object

StoFloor Cleanroom System 1 (StoPox BB OS)
Q-Id ST 1902-1095
Year 2019
Comments manufacturing date: 10/11/2018; color: RAL 7035; used material components: comp. A: 0050180311; comp. B: 0220180686; surface: smooth
Category Wall / Ceiling / Floor

Tests And Results

Subject of Test Parameter Assessment for / Results Documents
(valid to)
Particle emission (VDI 2083 part 17) Reel-on-disc test vs. PA6
normal force 300 N
ISO 14644-1 / ISO Class 4
certificate 1 en
(28-02-24)
QLogo 1 en
(28-02-24)
QLogo 2 en
(28-02-24)
statement 1 en
(28-02-24)
Outgassing (VDI 2083 part 17) Contaminant Category (x) VOC
SER 23 °C [g/m²s] 4.0E-7
SER 90 °C [g/m²s] 5.4E-4
ISO-ACCm Class (x) based on 23 °C / -6.4
certificate 1 en
(28-02-24)
QLogo 1 en
(28-02-24)
QLogo 2 en
(28-02-24)
statement 1 en
(28-02-24)
Contaminant Category (x) SVOC
SER 23 °C [g/m²s] not detectable
SER 90 °C [g/m²s] 2.8E-6
ISO-ACCm Class (x) based on 23 °C / < -9.6
Riboflavin test (VDMA information leaflet) Material tested StoFloor Cleanroom System 1 (StoPox BB OS)
Classification / exzellent
certificate 1 en
(28-02-24)
QLogo 1 en
(28-02-24)
QLogo 2 en
(28-02-24)
statement 1 en
(28-02-24)
Biological resistance (ISO 846) biological resistance Pilze (Prozedur A)
growth intensity 1
classification sehr gut
certificate 1 en
(21-10-24)
QLogo 1 en
(21-10-24)
QLogo 2 en
(21-10-24)
statement 1 en
(21-10-24)
biological resistance Bakterien (Prozedur C)
growth intensity 2
classification gut
biological resistance Gesamtergebnis
growth intensity 2
classification gut
Ab- / Desorption kinetic (VDI 2083 part 20 draft) Ø k-value 3.6 min
standard deviation 0.8 min
classification / nicht-absorptiv
certificate 1 en
(28-02-24)
QLogo 1 en
(28-02-24)
QLogo 2 en
(28-02-24)
statement 1 en
(28-02-24)