TESTED DEVICE®

No image available!

Company

Rockwool B.V., Rockfon (NL)
 
Industrieweg 15
6045 JG Roemond

Contact Person

Frank Winters
Phone (+31) 475 357672
Email frank.winters@rockfon.com
Website www.rockfon.com

Test Object

Medicare Block
Prototype
Q-Id RO 1212-627
Year 2012
Comments Dimensions: 595 mm x 595 mm x 25 mm Grid dimensions: 600 mm x 600 mm
Category Wall / Ceiling / Floor

Tests And Results

Subject of Test Parameter Assessment for / Results Documents
(valid to)
Particle emission (VDI 2083 part 9.1) Frequency (sinusoidal oscillation) 5 - 50 Hz
Oscillation velocity 0.1495 mm/s
Oscillation acceleration 0.083 mm/s²
Oscillation of the system 0.00047 mm
ISO 14644-1 / ISO Class 2
US FED 209E / US Class -
certificate 1 en
(08-03-18)
statement 1 en
(08-03-18)