TESTED DEVICE®

No image available!

Company

Tarkett AB
 
Ekenäsvägen 1
37281 Ronneby

Contact Person

Joacim Karlsson
Phone +46 (0) 457 71383
Email joacim.karlsson@tarkett.com
Website www.tarkett.com

Test Object

floor
iQ Granit SD
Q-Id TA 1304-646
Year 2013
Comments Batch number: 3096710 Color: 710
Category Wall / Ceiling / Floor

Tests And Results

Subject of Test Parameter Assessment for / Results Documents
(valid to)
Particle emission (VDI 2083 part 17) reel-on-disc test B12
counter specimen PA6
single measuring track 250 mm
velocity 150 mm/s
300 N
ISO 14644-1 / ISO Class 4
US FED 209E / US Class 10
EC-GMP Annex 1 (in Betrieb) / GMP Class A
certificate 1 en
statement 1 en
Outgassing (VDI 2083 part 17) temperature 23 °C
SER (siloxane) / - g/m²s
SER (amine) / - g/m²s
SER (organophosphate) / - g/m²s
SER (phthalate) / - g/m²s
SER (VOC) / 1.6 x 10 E-7 g/m²s
14644-8 / ISO-ACCm Class (VOC) -6.8
certificate 1 en
statement 1 en
temperature 90 °C
SER (siloxane) / not detectable g/m²s
SER (amine) / not detectable g/m²s
SER (organophosphate) / not detectable g/m²s
SER (phthalate) / not detectable g/m²s
SER (VOC) / - g/m²s
14644-8 / ISO-ACCm Class (VOC) -