Logo

Manufacturer/company:

Knauf Ceiling Solutions GmbH & Co. KG

Elsenthal 15
Grafenau
Germany

Number of projects
6
Number of test pieces
49
Phone

-

Email

-

Website

-

Documents

KN 2101-1202_Urkunde_05.pdf
Valid until 29.03.2026
KN 2101-1202_Bescheinigung_05.pdf
Valid until 29.03.2026
KN 2101-1202_certificate_05.pdf
Valid until 29.03.2026
KN 2101-1202_statement_05.pdf
Valid until 29.03.2026

Test piece

Name of test piece/s Armstrong Bioguard Acoustic 17 mm
Description Dimension: 600 x 600 x 17 mm
Project number KN 2101-1202
Created on 06/12/2025
Valid until 03/29/2026
Test type Particle emission (ISO 14644-1, -14)
Classfication Suitability for air cleanliness class: (ISO-Class):3
Particle emission (ISO 14644-1, -14)

Particle emission (ISO 14644-1, -14)

Test parameter(s)

Air Cleanliness Class

Structure-borne noise = approx. 5 to 50 Hz

3

Overall result

3


It should be noted that cleanrooms of class 1 to 5 according to ISO 14644-1 have a higher filter occupancy, which may restrict the use of ceiling systems. Cleanrooms with a horizontal displacement flow form an exception to this.
The test result may be affected by the surrounding ceiling system, in particular the material pairing between lights and ceiling frames, as well as other mounting accessories. Particle emission behavior should be reassessed in each assembly situation.

Please note: Transport damages, incorrect installation, aging behavior, corrosion etc. can influence the test result.