Logo

Manufacturer/company:

Teamtronic A/S

Kratholmvej 27B
Odense S
Denmark

Number of projects
1
Number of test pieces
4
Phone

+45 73 50 64 00

Email

mathias@teamtronic.dk

Website

www.teamtronic.dk/de/

Documents

TE 2502-1593_certificate_01.pdf
Valid until 28.05.2030
TE 2502-1593_statement_01.pdf
Valid until 28.05.2030

Test piece

Name of test piece/s In-line_95-75_ISO_600mm_PRM_RAL9016
Description Size: 600 x 93 x 78 mm; power: 16 W; lumen: 1481 lm
Project number TE 2502-1593
Created on 07/15/2025
Valid until 05/28/2030
Test type Particle emission (ISO 14644-1, -14)
Classfication Suitability for air cleanliness class: (ISO-Class):1
Particle emission (ISO 14644-1, -14)

Particle emission (ISO 14644-1, -14)

Test parameter(s)

Air Cleanliness Class

Structure-borne noise = approx. 50 Hz

1

Overall result

1


It must be pointed out, that according to ISO 14644-1 cleanrooms classes 1 to 5 have a high filter occupancy, with the result that large-surface ceiling/lighting systems cannot be used in some cases. Cleanrooms with a horizontal displacement flow form an exception to this.
The test result may be influenced by the surrounding ceiling system, in particular the material pairing between the light and ceiling frame, as well as other assembly accessories. Particle emission behavior should be re-assessed in the respective assembly situation. The cut edges/back are made of very porous material. Therefore, the use of the test piece in clean/hygienic areas is considered to be critical.

Please note: Transport damages, incorrect installation, aging behavior, corrosion etc. can influence the test result.